Explosion-proof junction box LEC end seal kit for heat tracing cable connection
LEC is an end seal kit designed for heat tracing cables, it confirms to IEC standards, all the materials involved in installation are arranged in the kit.
LEC end seal kit can be applied at hazardous locations Exell.
Tools required:
Steel wire pliers, screw driver, special bade.
Accessories required:
Gasket
Adhesive tape
GT-66 for installation temperature higher than 4ºC. GT66
GT-54 for installation temperature higher than -40ºC. GT54
Note:
1. This component is an electric device. It should be properly installed. Measures should be taken for fire protection.
2. Leakage protection device shall be installed to prevent fire as may happen due to damage or improper installation of heat tracing cables.
3. Only those parts and components approved according to our criteria can be used. Please don't use substitutes or PVC insulation tapes.
4. As the black conductive plastics is a conductor, it should strictly insulated and kept dry. Short circuit should be prevented.
5. In peeling the insulation layer or conductive plastics, please keep the bus wire intact as any damage of bus wire may lead to overheating or short circuit.
6. To prevent short circuit, bus wire shall never be contact with each other.